Feature:
* Fast measuring in the field
Within 20 minutes, 7 key fault gases and moisture can be read
* No consumables
Pure physical photo-acoustic spectroscopy technology,
The consumables of calibration gas and carry gas are needless.
* Moisture in the oil
The concentration of moisture in the oil can be given during the same one test,±1ppm
* Simple
Step-by-step software guides and touch screen, the user pass through the procedure.
* Portable and rugged
Weighs <10 Kg, in a rugged and convenient carry case.
* Reliable
Engineered design provides inherent reliability and high accuracy.
* DGA diagnosis
International general faults gases diagnosis method, preset the warning limits.
Roger's ratios, Duval's Triangle, IEEE key gases
* PC communication
* PC communication
External PCs is possible via USB connections, allowing databases to be imported or downloaded.
* Samples
Oil and gasTechnical Specification:
Gas | RANGE (ppm) | Resolution |
Hydrogen(H2) | 5.0~5000.0 | 2ppm NA |
Carbon Monoxide(CO) | 1.0~50,000.0 | 2ppm |
Carbon Dioxide(CO2) | 2.0~50,000.0 | 0.1ppm |
Ethylene(C2H4) | 1.0~50,000.0 | 0.1ppm |
Ethane(C2H6) | 1.0~50,000.0 | 0.1ppm |
Methane(CH4) | 1.0~50,000.0 | 0.1ppm |
Acetylene(C2H2) | 0.3~50,000.0 | 0.1ppm |
Acetylene(C2H2)Optional | 0.1~50,000.0 | 0.1ppm |
Water(H2O) | More than 5ppm | 2ppm NA |
Accuracy or tolerance : when valve <20ppm,±1ppm ;
while > 20ppm ,±10%
Oil sample :40ml±2ml; gas sample : 5ml±0.2ml
PC port : USB
Printing output : 2 inch mini printer
Power: 100~250VAC, 47~63Hz
Weight: 10Kg
Dimension : 524× 428 × 206 mm