- Higher performance Line to Line attenuation than the K Series
- E version meets the low leakage current requirements of VDE portable equipment and non-patient care equipment
- V version features same high performance
with more cost-effective design
Ordering Information
Available Part Numbers
1VDK1 | 1EDK1 |
1VDK3 | 1EDK3 |
3VDK1 | 3EDK1 |
3VDK3 | 3EDK3 |
6VDK1 | 6EDK1 |
6VDK3 | 6EDK3 |
10VDK1 | 10EDK1 |
10VDK3 | 10EDK3 |
20VDK1 | 20EDK1 |
20VDK6 |
Specifications
Maximum leakagecurrent, each Line to Ground: | |||
VDK Models | EDK Models | ||
@ 120 VAC 60 Hz | .4 mA | .22 mA | |
@ 250 VAC 50 Hz | .7 mA | .38 mA | |
Hipot rating (oneminute): | |||
Line to Ground | 2250 VDC | ||
Line to Line | 1450 VDC | ||
Operating Frequency: | 50 / 60 Hz | ||
Rated voltage(max.): | 250 VAC | ||
Rated Current: | 1A to 20A | ||
Operating Ambient Temperature Range(at rated current Ir): | |||
-10°C to +40°C | |||
In an ambienttemperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir √(85-Ta)/45 |
Electrical Schematic
Case Styles
VDK1 / EDK1
Typical Dimensions: | ||
Line/Load Terminals(4): | .250 [6.3] with .07 [1.8] Dia. hole | |
Ground Terminal(1): | .250 [6.3] with .07 x .16 [1.8 x 3.8] slot | |
Mounting Holes (2): | .188 [4.75] Dia. |
VDK3 / EDK3
Typical Dimensions: | ||
Wire leads (5): | .4.0 [101.6] Min. AWG18 (AWG16 for 10A) | |
Mounting Holes (2): | .188 [4.75] Dia. |
20VDK1 / 20EDK1
Typical Dimensions: | ||
Line/Load Terminals(4): | .250 [6.3] with .07 [1.8] Dia. hole | |
Ground Terminal(1): | .250 [6.3] with .07 x .16 [1.8 x 3.8] slot | |
Mounting Holes (2): | .188 [4.75] Dia. |
20VDK6
Case Dimensions
Typical Dimensions: | ||
Terminals (5): | 8-32 Torque 18 lbf-in. [2.03 N-m] max. ±2[.22] | |
Mounting Holes (2): | .188 [4.75] Dia. |
Case Dimensions
Part No. | A | B | C | D | E |
(max.) | (max.) | (max.) | ± .015 | (max.) | |
±.38 | |||||
1VDK1, 1EDK1 | 3.35 | 2.07 | 1.16 | 2.375 | 2.81 |
85.1 | 52.6 | 29.5 | 60.33 | 71.4 | |
1VDK3, 1EDK3 | 2.07 | 2.07 | 1.16 | 2.375 | 2.81 |
52.6 | 52.6 | 29.5 | 60.33 | 71.4 | |
3VDK1, 3EDK1, 6VDK1, 6EDK1 | 3.85 | 2.07 | 1.16 | 2.938 | 3.35 |
97.8 | 52.6 | 29.5 | 74.63 | 85.1 | |
3VDK3, 3EDK3, 6VDK3, 6EDK3 | 2.56 | 2.07 | 1.16 | 2.938 | 3.35 |
65.0 | 52.6 | 29.5 | 74.63 | 85.1 | |
10VDK1, 10EDK1 | 3.85 | 2.07 | 1.32 | 2.938 | 3.35 |
97.8 | 52.6 | 33.5 | 74.63 | 85.1 | |
10VDK3, 10EDK3 | 2.57 | 2.07 | 1.32 | 2.938 | 3.35 |
65.3 | 52..6 | 33.5 | 74.63 | 85.1 | |
20VDK1, 20EDK1 | 3.85 | 2.58 | 1.78 | 2.938 | 3.35 |
97.8 | 65.5 | 45.2 | 74.63 | 85.1 | |
20VDK6 | 3.46 | 2.58 | 1.78 | 2.938 | 3.35 |
87.9 | 65.5 | 45.2 | 74.63 | 85.1 | |
Performance Data
Typical Insertion Loss
Measured in closed 50 ohm system
Typical Insertion Loss
Measured in closed 50 ohm system
1 & 3VDK
6, 10, 20 VDK
1 & 3EDK
6, 10, 20 EDK
Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
Common Mode / Asymmetrical (Line to Ground)
Differential Mode / Symmetrical (Line to Line)
Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
Common Mode / Asymmetrical (Line to Ground)
Current Rating | Frequency - MHz | |||||
.15 | .5 | 1 | 5 | 10 | 30 | |
VDK Models | ||||||
1A, 3A | 18 | 30 | 40 | 48 | 48 | 40 |
6A, 10A,20A | 10 | 22 | 30 | 39 | 44 | 50 |
EDK Models | ||||||
1A, 3A | 17 | 27 | 33 | 45 | 45 | 40 |
6A, 10A,20A | 10 | 19 | 25 | 34 | 40 | 46 |
Differential Mode / Symmetrical (Line to Line)
Current Rating | Frequency - MHz | |||||
.15 | .5 | 1 | 5 | 10 | 30 | |
VDK, EDK Models | ||||||
1A, 3A | 18 | 47 | 62 | 60 | 50 | 45 |
6A, 10A,20A | 20 | 43 | 55 | 65 | 60 | 55 |