127/220KV Copper Conductor, XLPE insulation Corrugated Aluminum Metalic Sheath and PVC Sheath EHV Cable
High Voltage Power Cable 110~220KV Australia Standard Cable
Brief introduction of the 110~220KV XLPE High Voltage XLPE Insulated Australia Standard Cable products:
1. The cross-linkage PE insulated and wrinkled aluminum wrapper waterproof PVC sheathed power cable.
Type |
YJLW02, YJLLW02 |
Specification |
240mm2~3000mm2 |
Voltage |
110~220KV |
Usage |
Suitable for the places with a higher underground water level and to be used underground, in the tunnels or pipes. Such cables bear a bigger pulling force and pressure. |
2. The cross-linkage PE insulated and wrinkled aluminum wrapper waterproof PE sheathed power cable.
Type |
YJLW02, YJLLW02 |
Specification |
240mm2~3000mm2 |
Voltage |
110~220KV |
Usage |
Suitable for the places with a higher underground water level and to be used underground, in the tunnels or pipes. Such cables bear a bigger pulling force and pressure. |
Specific property for usage of 110KV~220KV XLPE High Voltage Australia Standard Cable :
1. Cable’s conductor highest working temperature is allowed up to 90°C, and overload when meet an emergency is 130°C , When short circuit (in ≤5 seconds) the highest temperature is 250°C
2. When installing or laying cable, the ambient temperature should be less than -20°C, and have to give a preheat to cable.
3. The minimum bending diameter:
Cable type Bending diameter |
Metal sheathed |
After laying |
30D0 |
During laying |
40D0 |
Note: In form, D0 is a real test value to cable’s outer diameter.
4. Allowed biggest axial traction force to outer diameter when laying cable (not consider the radial lateral-pressure at bent set ion) T=K×core NO. ×section (kg), in formula, the coefficient K value should be: the copper core get 7, the aluminum core get 4.
5. Allowed biggest lateral-press P, when cable is being bent
The single core cable is required P≤500kg/m.
P=T/R (T is indicated axial traction force; R is indicated radius of bent-wheel), Knowing from above formula, as the traction force is made up by length and weight of cable. So it lets P to applying requirement as above. Then the diameter of bent-wheel should be widened.
6. Cable laying is not being restricted by drop.