Specifications
Power supply |
230VAC/110VAC/24VAC selectable in the order |
Output |
One or two Max. 5A relay/each for the On/Off output |
Displaying |
LCD |
External sensor connection |
Typical 2m, 4m/6m/8m selectable |
Net weight |
280g |
Dimensions |
120mm(L)×90mm(W)×32mm(H) |
Mounting standard |
Wall mounting in the wire box of 2”×4” or 65mm×65mm |
Sensor spec. |
Temperature |
Humidity |
Accuracy |
±0.5 (20~40) |
±4.0% RH (20%-80%RH), 25 |
Measuring range |
0~60 |
0~100%RH |
Display resolution |
0.1 |
0.1%RH |
Stability |
<0.04/year |
<0.5%RH/year |
Storage environment |
10-50, 10%~70%RH |
Description
1. Detecting and display ambiance relative humidity& temperature
2. A high accuracy RH & Temp. sensor inside
3. LCD can display working status such as %RH, temperature, set point, and device mode, etc. Makes reading and operating easy and accurate
4. Provide one or two dry contact outputs to control a Humidifier/dehumidifier and a cooling/heating device
5. All models feature user-friendly setting buttons
6. Enough parameters setup for end users for more applications. All setup will be held even if power failure
7. Button-lock function avoids wrong operation and keep on the setup
8. The end user can adjust setpoint via buttons, and can set cooling/heating mode, humidify/dehumidiry mode via DIPs
9. End user even can set differencial in Advance Setup. Which is a programmable unit.
10. Infrared Remote Control (optional)
11. Blue backlight (optional)
12. Modbus RS485 interface (optional)
13. Provide the controller with an external RH&Temp. sensor or external RH&Temp. sensor box
Applications
-
High end HVAC systems
-
Ventilation systems
-
Detection and display temperature and RH measurements
-
Control temperature and humidity devices
-
Modbus communication systems
Buttons and LCD
Wiring diagram
Models Guide
Product Name |
Model |
Description |
Humidity Controller |
F2000P-TH-K01-a-(A)/(B)/(C) |
Detect and display RH&Temp. 1XON/OFF relay output to control a humidifier or dehumidifier. The max. current is 5A. |
F2000P-TH-K02-a-(A)/(B)/(C) |
Detect and display RH&Temp. 2 ON/OFF relay outputs to control a humidifier/ dehumidifier and a cooling/heating device. The max. current is 5A. |
|
F2000P-TH-K01-WT-(A)/(B)/(C) |
Detect and display RH&Temp. with the external sensor. 1XON/OFF relay output to control a humidifier or dehumidifier. |
|
F2000P-TH-K02-WT-(A)/(B)/(C) |
Detect and display RH&Temp. with the external sensor. 2 ON/OFF relay outputs to control a humidifier/ dehumidifier and a cooling/heating device. |
|
F2000P-TH-K01-TSM-(A)/(B)/(C) |
Detect and display RH&Temp. with an external sensor box. 1XON/OFF relay output to control a humidifier or dehumidifier. |
|
F2000P-TH-K02-TSM-(A)/(B)/(C) |
Detect and display RH&Temp. with an external sensor box. 2X ON/OFF relay outputs to control a humidifier/ dehumidifier and a cooling/heating device. |
|
Humidity Controller |
F2000PC-TH-K01-(A)/(B)/(C) |
Detect and display RH&Temp. 1XON/OFF relay output to control a humidifier or dehumidifier. Modbus interface |
F2000PC-TH-K02-(A)/(B)/(C) |
Detect and display RH&Temp. 2 ON/OFF relay outputs to control a humidifier/ dehumidifier and a cooling/heating device. Modbus interface. |
|
Options for Above Models |
||
Options |
Back light-EL |
Blue back light displaying |
Remote receiving-R |
Remote control humidity with the infrared hand held controller |