High Volume HEPA filter for Cleanroom Terminal Filtration H13 H14 EN:1822
Specifications for high volume HEPA filters;
- Stainless steel, galvanized steel, AL board, plastic frame, rigid box design, V cell mini pleated EHPA filter; Double or triple air flow rate more than same size HEPA filter with separator;
- Superfine glass fiber filter media, HV company glass fiber also available; Mini pleated filter media offer large air filter area, high air flow rate, large dust holding capacity, low pressure drop;
- Construction design: box, flange, double flange; 3V, 4V, 5V, 6V available;
- Standard size: 610*610*292 mm, 310*610*292 mm, 595*595*292 mm, 287*595*292 mm; other size can be customized;
- Filter efficiency range: F6 – F9 EN:779; H10 – H14 EN:1822;
- Sealant: polyurethane around the perimeter;
- Gasket: dove detailed neoprene, air inlet or outlet side, both side also OK; gasket thickness 5mm;
- Separator in mini pleated filter pack are hot-melt that anti bacterial and anti mold;
Application:
1. HVAC terminal HEPA filtration;
2. Commercial buildings HVAC system such as hospital, school, library, airport and so on;
Features:
High air flow rate, low pressure drop, HV company glass fiber make sure good performance;
high efficiency 99.99% @ 0.3um
All HEPA filters will be tested before leave the factory, test according to MPPS;
Data Sheet:
Size | Efficiency | Air Flow Rate | Pressure drop |
610*610*292 mm - 5V | H13 | 3600 m³/h | 250 Pa |
310*610*292 mm - 5V | H13 | 1800 m³/h | 250 Pa |
595*595*292 mm - 5V | H13 | 3000 m³/h | 250 Pa |
287*595*292 mm - 5V | H13 | 1500 m³/h | 250 Pa |
Pressure drop range: ±15%
According to clients` requirements offer different specifications