- Compact EMI filter with IEC 60320-1 C14 Inlet
- Enhanced two element circuit provides medium attenuation to 30MHz
- Compact and cost-effective design
- Supersedes most ED Series versions
- Includes 20A version with standard IEC 60320-1 C20 inlet
- Several termination styles
- Flanged mounting
EJS Models
- Same performance as the EEJ Series
- Snap-in mounting
- Several termination styles
- Includes 20A version with standard IEC 60320-1 C20 inlet
EJH & EJHS Models
- Minimal leakage current suitable for patient-contact medical applications
- Flanged mounting the same as the EEJ Series
- Also available in snap-in versions (EJHS)
- Two element circuit provides modest EMI attenuation above 1MHz
- Capacitive input (refer to the H Series for capacitive output)
- EJHS models feature snap-in mounting
EJM & EJMS Models
- Low leakage current, suitable for most medical applications
- Improved EMI attenuation up to 200MHz
Mechanically the same as the EEJ Series with flange or snap-in mounting - EJMS models feature snap-in mounting
Ordering Information
Available Part Numbers
EEJ Models | EJH Models |
1EEJ1 | 1EJH1 |
1EEJ2 | 1EJH2 |
1EEJP | 1EJHP |
1EEJ8 | 1EJH8 |
3EEJ1 | 3EJH1 |
3EEJ2 | 3EJH2 |
3EEJP | 3EJHP |
3EEJ8 | 3EJH8 |
6EEJ1 | 6EJH1 |
6EEJ2 | 6EJH2 |
6EEJP | 6EJHP |
6EEJ8 | 6EJH8 |
10EEJ1 | 10EJH1 |
10EEJ2 | 10EJH2 |
10EEJP | 10EJHP |
10EEJ8 | 10EJH8 |
15EEJ1 | 15EJH1 |
15EEJ2 | 15EJH2 |
15EEJP | 15EJHP |
15EEJ8 | 15EJH8 |
20EEJ1 | 20EJH1 |
20EEJ8 | 20EJH8 |
EJS Models | EJHS Models |
1EJS1 | 1EJHS1 |
1EJS8 | 1EJHS8 |
3EJS1 | 3EJHS1 |
3EJS8 | 3EJHS8 |
6EJS1 | 6EJHS1 |
6EJS8 | 6EJHS8 |
10EJS1 | 10EJHS1 |
10EJS8 | 10EJHS8 |
15EJS1 | 15EJHS1 |
15EJS8 | 15EJHS8 |
20EJS1 | |
20EJS8 | |
EJM Models | EJMSModels |
1EJM1 | 1EJMS1 |
1EJM8 | 1EJMS8 |
3EJM1 | 3EJMS1 |
3EJM8 | 3EJMS8 |
6EJM1 | 6EJMS1 |
6EJM8 | 6EJMS8 |
10EJM1 | 10EJMS1 |
10EJM8 | 10EJMS8 |
15EJM1 | 15EJMS1 |
15EJM8 | 15EJMS8 |
Specifications
Maximum leakagecurrent, each Line to Ground: | ||||
EEJ/EJS | EJH | EJM | ||
@ 120 VAC 60 Hz | .22 mA | 2 µA | .01 mA | |
@ 250 VAC 50 Hz | .38 mA | 5 µA | .017 mA | |
Hipot rating (oneminute): | ||||
Line to Ground | 2250 VDC | |||
Line to Line | 1450 VDC | |||
Operating Frequency: | 50 / 60 Hz | |||
Rated voltage(max.): | 250 VAC | |||
Rated Current: | 1A to 20A | |||
Operating Ambient Temperature Range(at rated current Ir): | ||||
-10°C to +40°C | ||||
In an ambienttemperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir √(85-Ta)/45 |
Electrical Schematic
Accessories
GA400: NEMA 5-15P to IEC 60320-1 C13 line cord
FA601: Insulating Shroud
EJS Models
Case Styles
EEJ1, EJH1 & EJM1 (1-15A)
FA601: Insulating Shroud
EJS Models
Case Styles
EEJ1, EJH1 & EJM1 (1-15A)
Typical Dimensions: | ||
Mounting holes (2): | .132 [3.35] Dia. with .236 [5.99] Dia. x 90º countersink for #4 flathead screw | |
Line Inlet (1) | IEC60320-1 C14 | |
Terminals (2): | .250 [6.35] with .07 [1.8] Dia. hole | |
Ground Terminal (1): | .250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
EEJ2 & EJH2 (1-15A)
Typical Dimensions: | ||
Mounting holes (2): | .132 [3.35] Dia. with .236 [5.99] Dia. x 90º countersink for #4 flathead screw | |
Line Inlet (1) | IEC60320-1 C14 | |
Terminals (2): | .250 [6.35] with .07 [1.8] Dia. hole | |
Ground Terminal (1): | .250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
EEJP & EJHP (1-15A)
Typical Dimensions: | ||
Mounting holes (2): | .132 [3.35] Dia. with .236 [5.99] Dia. x 90º countersink for #4 flathead screw | |
Line Inlet (1) | IEC60320-1 C14 | |
PC board pins (3): | .031 [.07] square, ± .003[.07] |
EJS1, EJHS1 & EJMS1 (1-15A)
Typical Dimensions: | ||
Line Inlet (1) | IEC60320-1 C14 | |
Terminals (2): | .250 [6.35] with .07 [1.8] Dia. hole | |
Ground Terminal (1): | .250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
EEJ8, EJH8 & EJM8 (1-15A)
Typical Dimensions: | ||
Mounting holes (2): | .132 [3.35] Dia. with .236 [5.99] Dia. x 90º countersink for #4 flathead screw | |
Line Inlet (1) | IEC60320-1 C14 | |
Wire Leads (3): | 4.0 [101.6] Min. 18AWG, UL1015 |
EJS8, EJHS8 & EJMS8 (1-15A)
Typical Dimensions: | ||
Line Inlet (1) | IEC60320-1 C14 | |
Wire Leads (3): | 4.0 [101.6] Min. 18AWG, UL1015 |
20EEJ1 & 20EJH1
Typical Dimensions: | ||
Mounting holes (2): | .132 [3.35] Dia. with .236 [5.99] Dia. x 90º countersink for #4 flathead screw | |
Line Inlet (1) | IEC60320-1 C20 | |
Terminals (2): | .250 [6.35] with .07 [1.8] Dia. hole | |
Ground Terminal (1): | .250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
20EJS1
Typical Dimensions: | ||
Line Inlet (1) | IEC60320-1 C20 | |
Terminals (2): | .250 [6.35] with .07 [1.8] Dia. hole | |
Ground Terminal (1): | .250 [6.35] with .07 x .16 [1.8 x 4.1] slot |
20EEJ8 & 20EJH8
Typical Dimensions: | ||
Mounting holes (2): | .132 [3.35] Dia. with .236 [5.99] Dia. x 90º countersink for #4 flathead screw | |
Line Inlet (1) | IEC60320-1 C20 | |
Wire Leads (3): | 4.0 [101.6] 14AWG, UL1015 |
20EJS8
Typical Dimensions: | ||
Line Inlet (1) | IEC60320-1 C20 | |
Wire Leads (3): | 4.0 [101.6] 14AWG, UL1015 |