The cable is used for the link line of electrical equipment and apparatus withthe voltage not exceeding 450/750V. The mechanical, physical and electricalcharacteristics are referenced by the standard required inGB/T9330-2008 Plastic-insulated Control Cables (thenational standard of China)
use characteristic and the main index of electrical characteristics
a) Installationtemperature:≥0°C
b) Long-term permissible operationtemperature 70°C
c) Minimum bending radius:
a:The unarmored cables should exceed the 6D
b:The armored cables should exceed 12D
C:The flexible cables with shield construction should exceed6D.
d) The finished cables should experience theAC 50HZ test and 3000v voltage test, not broken in 5min..
e) The DCRcomply with the rules ofGB/T3956-2008 The Conductor of Cables(the national standard of china)
Type, Name, Suitable areas
Type | Name | Suitablefor |
KVV | PVC insulated and sheathed control cablewith copper-conductor | The fixed areas such as indoor, cablechannel, pipeline and soon |
KVVP | PVC insulated and sheathed control cablewith copper-conductor and braidingshield | The fixed areas requiring shield such asindoor, cable channel pipeline andso on. |
KVVP2 | PVC insulated and sheathed control cablewith copper-conductor and coppertape shield | The fixed areas requiring shield such asindoor, cable channel pipeline andso on. |
KVV22 | PVC insulated and sheathed control cablewith copper-conductor and steeltape shield | The fixed areas bearing lager mechanicalforce such as indoor, cablechannel, pipeline, direct burial ground and soon. |
KVV32 | PVC insulated and sheathed control cablewith copper-conductor and thinsteel wire shield | The fixed areas bearing lager mechanicalforce such as indoor, cablechannel, pipeline, vertical shaft and so on. |
KVVR | PVC insulated and sheathed control flexible cord withcopper-conductor | The indoor areas requiring flexible andmovable |
KVVRP | PVC insulated and sheathed control flexiblecord with copper-conductor andbraiding shield | The indoorareas requiring flexible,movable and shielded |
KVVP2-22 | PVC insulated and sheathed control cablewith copper-conductor, copper tapeshielded and armored | The fixed and shielded areas bearing lagermechanical force such as indoor,cable channel, pipeline and so on. |
KVVP3 | PVC insulated and sheathed control cablewith copper-conductor andlaminated AL-plastic shield | The fixed and shielded areas such asindoor, cable channel, pipeline and soon. |
Production Range
Type | (v) Ratedvoltage | (mm2) Standardconductor cross-section area | |||||||||
0.5 | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | ||||
core number | |||||||||||
KVV KVVP | 450/750 | -- | 2-61 | 2-14 | 2-10 | ||||||
KVVP2 KVVP3 | -- | 4-61 | 4-14 | 4-10 | |||||||
KVV22 | |||||||||||
-- | 7-61 | 4-61 | 4-14 | 4-10 | |||||||
KVVP2-22 | |||||||||||
-- | 19-61 | 7-61 | 4-14 | 4-10 | |||||||
KVV32 | |||||||||||
2-61 | -- | -- | |||||||||
KVVR | 2-61 | 2-48 | -- | -- | |||||||
KVVRP | |||||||||||
Note: the recommended core number:2,3,4,5,7,8,10,12,14,16,19,24,27,30,37,44,48,52 and 61.
Control cable