the cable meet the standard of GB9330-88 or IEC227(1979).
it is suitable for connection of electric apparatus and instrument in electricity distriution equipment with A.C. rated voltage upto 500v/750v or D.C.1000V
2. type and designation
Ordinary type | Flame resistant type | Designation |
KVV | ZR-KVV ZRB-KVV ZRA-KVV | Cu conductor, PVC insulated and sheathed control cables |
KVV22 | ZR-KVV22 ZRB-KVV22 ZRA-KVV22 | Cu conductor, PVC insulated, PVC sheathed and tape (steel wire) armored control cables |
KVVP | ZR-KVVP | Cu conductor, PVC insulated, PVC sheathed and copper wire braid control cables |
KVVP2 | ZR-KVVP2 | Cu conductor, PVC insulated, PVC sheathed and copper tape shielded control cables |
KVVP2-22 | ZR-KVVP2-22 | Cu conductor, PVC insulated, PVC sheathed, copper tape shielded and steel tape armored control cables |
Note: The control cable of flame retardant type is mainly used in the place where fire-proof performance is required. The cable compiles to the requirement of the combustion test of GB12666.5-90 or IEC60332-3:2000. The ZR, ZRA and ZRB represent, respectively, flame retardant Category C, Category A and Category B. The cable can be produced with steel tape or steel wire armor.
4.specifications
4.specifications
Type | (mm2) Nominal Cross-sectional Area | Number of cores |
KVV ZR-KVV KVVP KVVP2 ZR-KVVP ZR-KVVP2 | 1.0,1.5,2.5 | 2,3,4,5,6,7,8,10,12,14,16,19,24,27,30,37,41,44,48,52,61 |
4.6 | 2,3,4,5,7,8,10,14 | |
10 | 2,4 | |
KVV22 ZR-KVV22 KVVP2-22 ZR-KVVP2-22 | 1.0,1.5,2.5 | 7,8,10,12,14,16,19,24,27,30,37,41,44,48,52,61 |
4.6 | 4,5,7,8,10,14 |
5.using propertities
The maximum operating temperature of the conductors shall not exceed 70℃. Installation temperature of the cable shall not be below 0℃.The laying bending radius shall not be less than 10 times the outer diameter of the cable.