GDKC-2000 On load tap changer ohmmeter analyzer
1.Introduction
On load tap changer analyzer GDKC-2000 is mainly applied to test transient time, transition waveform, transition resistance, synchronization status of three phase.
2.Test feature
①. Test transformers of type Y0 Y △ and display resistance value directly;
②. Automatically analyze waveform fault and mark the fault.
③. Automatically adjust resistance value and time range according to sampling data
④. Transformer type △ is able to display to synchronization status of three phase;
⑤. Be able to test with winding or without winding;
⑥. Four terminal connection mode and provide high accuracy of resistance measurement.
⑦. Continuous test to save time of power off
⑧ Make word report
⑨. 800×480 colorized LCD with touch screen and high speed printer
⑩. Store 1000 groups of data and also can be saved by USB flash disk
3.Technical parameters
Three phase constant current source charge,charge current | 3A/1A; 0.6A/0.2A |
Maximum voltage of the port | 24V |
Maximum range of transition resistance | 100Ω |
Record time of waveform | 300ms |
Sample rate | 30k |
Resolution of time | 0.1ms |
Resolution of resistance | 0.1Ω |
Accuracy of transition resistance | ±5% Reading±0.1Ω |
Accuracy of transient time | ±0.5% Reading±0.2mS |
Temperature | -10-40℃ |
Humidity | <85%RH |