GDVA-405 Made in China CT PT Transformer Tester

Payment Terms: T/T,L/C,WU
Trade on HiSupplier, Worry Free Guarantee
Trading safety, secure your money, lower the risk, protect both buyers and suppliers
HiSupplier is a Chinese multinational company in U.S, it helps to coordination and order landing.
More ›
  • Product Details
  • Company Profile
  • Product Reviews
Basic Info.
  • Place of Origin: Chongqing  
  • Min.Order: 1 Set/Sets

  GDVA-405 Made in China CT PT Transformer Tester 

 

                                   

Application

Tests for current transformer

Tests for voltage transformer

Applications for CTPT analyzer

Excitation curve and parameters test

Turns ratio test

CT nameplate check

Turns ratio test

Phase angle error test

CT parameters check in work burden

Ratio and phase error test

Polarity test

CT transient parameters analysis

Polarity mark check

Secondary burden test

CT ratio and phase error calibration

Coil resistance measurement

Coil resistance test

PT routine test

Secondary loop burden measurement



Error line curve test for protection CT



Transient CT parameters test



CT nameplate guess



Saturation hysteresis loop curve measurement



 

Specifications:

♦ Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13

♦ Power supply: AC220V±10%,50Hz/60Hz±10%

♦ Power output: 0.1~180V (AC)

 ♦ Current output: 0.001~5A(RMS)

 ♦Power output:300VA

 ♦Maximum knee voltage measurement; 45kv

 ♦Current measurement:

  • Range:0~10A (automatically change range in 0.1/0.4/2/10A)           

  • Error <±0.1%+0.01%FS

  •  ♦   Voltage measurement:

  • Range:0~200 V (automatically change range in 1V/10V/70V/200V)

  • Error < ±0.1%+0.01%FS

  •  ♦   Turns ratio measurement:

  • Range :1~35000,

  • 1~2000 error<0.05%

  • 2000~5000 error>0.1%

  • 5000~35000 error<0.2%

  •  ♦  Phase measurement: error:±2min,resolution:0.01min

     ♦   Coil resistance measurement:

  • Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm /800ohm /8kohm)

  • Error< 0.2%RDG+0.02%FS

  • Maximum resolution:0.1mΩ

  •  ♦   Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree

     ♦  CT Secondary burden:

  • Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

  • Error <0.2%RDG+0.02%FS

  • Maximum resolution 0.001ohm

  •  ♦   PT Secondary burden:

  • Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)

  • Error <0.2%RDG+0.02%FS

  • Maximum resolution: 0.1ohm

  •  ♦   PT ratio measurement:

  • Range :1~35000,

  • 1~5000 error<0.2%

  • 5000~35000 error<0.5%

  •  ♦   Saved data groups:>1000groups

     ♦   Work condition: Temperature:-10℃~50℃, moist:≤90%

     ♦   Size: 485mm×356mm×183mm

     ♦   Weight: <15Kg

     

    Testing Report 


     

     



Send message to this supplier
Ms. Sunny
Tel: 86-23-62984892
Enter between 20 to 3,000 chatacters.
Contact Method
Gold Mechanical & Electrical Equipment Co.,Ltd
9F/10,Jintai Building ,Nanping,, Chongqing, China (Mainland)
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!
Buyer Help Center