IEC60898 Standard 6KA Miniature circuit breaker DZ47-63-Q2 mcb 1P 2P 3P 4P
Key Specification
- CE/CB/ISO9001/CCC certificates;
- Rated voltage:230/400VAC;
- frequency50/60Hz;
- Rated current:1,3,6,10,16,20,25,32,40,50,63A;
- 1/2/3/4poles optional;
- Mechniacal life:20,000times;
- Flame-redardant:PA66 nylon material;
- Protection degree:IP20;
- With over load/short circuit protection;
- Standard:IEC60898;
- Enduring tem.30°C
- Breaking Capacity:4/6KA;
- Lighting/Motor protection optional
APPLICATION
DZ47-63-Q2 high breaking miniature circuit breaker has the features of structure advanced, performance reliable, breaking capacity high, appearance elegant and its shell and parts are made of material with impact resistance, strong flame-retardant feature.
It is suitable to power system of 50or 60 frequency ,Ue 400V and below, Ui 63A and below.
It is mainly applied at office building, residence, for lighting , power distribution and overload and short circuit protection of equipment. Normally, it also can be used as the not frequent transfer of power system. It conforms to the standards IEC60898and GB10963.1.
TECHNICAL PARAMETERS
Rated voltage (V) |
Poles |
Rated current (A) |
Rated short circuit breaking capacity |
|
Test breaking capacity(KA) |
Power factor |
|||
230 |
1,2 |
6,10,16,20, 25,32, 40 |
6 |
0.65~0.70 |
230/400 |
1,2 |
6 |
||
400 |
2,3,4 |
6 |
||
230 |
1,2 |
50,63 |
4.5 |
0.75~0.80 |
230/400 |
1,2 |
4.5 |
||
400 |
2,3,4 |
4.5 |
Remark:
1) mechanical life:20,000 times(off-on)
2) heat resistance: category 2 (temperature 55°C,relative humidity 95%).
3) wiring is terminal with clamp, cable dia.:25mm2
CURRENT RELEASE CHARACTER DIAGRAM
Test current(A) |
Rated current(A) |
Requested time |
Result |
Start station |
Remark |
1.13In |
all |
t>=1h |
Don’t trip |
Cool |
|
1.45In |
All
Didn't find what you're looking for?
Post Buying Lead or
contact our customer service specialist for help!
|