Applicable standards: GB1094.1-1996 GB1094.3-2003 GB/T 6451-2008 IEC60076
Model: S9-M-400KVA
Voltage ratio: 11kv-0.4kv
Vector group: YYNO or DYN11
Tapping rang: +-5%
Impedance voltage: 4%
No-load current: 1.3%
No-load loss: 570W
Load loss: 4300w
Active part weights: 910kg
Oil weights: 225kg