Porcelain Transformer Surge Arrester / 5KA Line Surge Arrester

 

 

Specifications:

 

Type Rate voltage kv Maximum continous operation voltage kv Continous operation voltage kv 1.2/50us lightning current KV≥ 8/20 us Lightning current impulse KV ≥ 2000us Square wave current impulse KV 4/10us High current impulse kA
Y5C-3 3 2.55 5 7.8 9 100 65
Y5C-6 6 5.1 10 15.5 18 100 65
Y5C-9 9 7.65 16.5 24.5 27 100 65
Y5C-10 10 8.4 18 27.2 30 100 65
Y5C-12 12 10.2 21 32.6 36 100 65
Y5C-15 15 12.7 25 38.8 45 100 65
Y5C-18 18 15.3 31 48.1 54 100 65
Y5C-21 21 17 34 52.7 63 100 65
Y5C-24 24 19.2 39 60.5 75 100 65
Y5C-27 27 21.9 45 69.8 81 100 65
Y5C-30 30 24.4 50 77.5 90 100 65
Y5C-33 33 26.8 55 85.3 99 100 65
Y5C-36 36 29 60 93 108 100 65
Y5C-42 42 34.1 70 108.5 126 100 65

 

 
Description:
 
Arrester is a kind of overvoltage protector mainly applied for the protechtion of various electrical appliances (such as transformer, switch, capacitor, trap, mutual inductor, generator, motor and power cable etc.) in power system, railway electrification system and communication system from being damaged by atmosphere overvoltage, operation overvoltage and power frequency temporary overvoltage etc.
 
The product characteristic:
 
1.Smaller in size,Light in weight,High withstand collision,Flexible installation, Particularly suitable for use in the switch cabin
2.Special structure, the overall compression molding, no air gap, high sealing performance, moisture-proof explosion-proof
3.Long creepage distance , good hydrophobic, strong resistance to incompetence, stable performance and reduce operation and maintenance
4.Zinc oxide resistor disc in special formula,small leak age current,slow aging speed ,long service life
5.Real with DC reference voltage, square-wave-pass flow capacity and high current tolerance is higher than the national standard.
 
User Notice:
 
1.Before installation,the arresters shall be stored in clean and dry rooms and kept away form the corrosions by corrosive gas or liquid.
2.Before put into operation,preventative testing shall be made on the arrester.And after the arrester has been put into operation,regular testing shall be made as follows and follows and comparison shall be made with the data before the operation according to the attached table.(Every 5 years for arrester of 10kV or under,and every 2 year for arrester of 35kV and above)
a.Measure the insulation resistance of the arrester;
b.Measure the reference voltage of the arrester under direct current of 1mA 
c.Meausre the leak age current under the reference voltage of 0.75 time direct current of 1mA
 
Features:
 
1. Compact and Lightweight
2. Extremely Safe Pressure Relief Performance
3. Superior Performance against Environmental Contamination
4. Directly Molded Structure
5. Compliance with International Standards(IEC60099-4)
6. Simple Support Structure
7. Manufactured at Advanced ISO-9001 certified facilities
 
Used in:
1. Distribution networks
2. Transmission line
3. Substation
4. Railway power station
5. Alternator and electromotor
 

 

 

 



 
 
 


Send message to this supplier
Mr. Mrs. Vivian
Tel: 86-577-62785181
Enter between 20 to 3,000 chatacters.
Contact Method
YIXIN ELECTRICAL EQUIPMENT CO.,LTD
No.218 Wei San Road YueQing Economic Development Zone,undefined,undefined, Wenzhou, Zhejiang, China (Mainland)
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!
Buyer Help Center