0.6/1kV XLPE Insulated Power Cable
Standards
The cable meets the standard requirements of GB/T12706-2002 or IEC60502-1997. It is suitable to be installed in the power line with rated voltage of 0.6/1kV U0/U (Um).
Type, Designation and Applications
Type
Designation
Applications
YJV
YJLV

Cu or Al conductor XLPE insulated PVC sheathed power cable
For laying indoors, in tunnel and in ducts. Able to bear certain traction during laying but not external mechanical forces. Impermissible to lay single core cable in magnetic ducts.
YJV22
YJLV22

Cu or Al conductor XLPE insulated PVC sheathed internal steel tape armored power cable.
For laying indoors, in tunnels, in ducts and underground. Able to bear external mechanical force but not large pulling forces. Impermissible to use single cable in A.C. circuit.
Specifications
Type
Number of cores
Nominal Cross-sectional Area(mm2)
YJV YJLV
1
1.0~630
YJV YJV22
YJLV YJLV22
2
1.0~400
YJV YJV22
YJLV YJLV22
3
1.0~400
YJV YJV22
YJLV YJLV22
3+1
4.0~400
YJV YJV22
YJLV YJLV22
4
1.0~400
YJV YJV22
YJLV YJLV22
5
1.0~400
Using properties
1.The maximum rated temperature
The maximum operating temperature of cores shall not exceed 90℃ when the cable is used for long period. The temperature of cores shall not exceed 250℃ at short circuit for 5 seconds.
2. Installation requirement
The installation of cables is not limited by the difference of level along the route. The ambient temperature should not be below 0℃ during installation. The permissible bending radius for cable shall not be less than 10 times of the cable diameter. The single cable shall be without amour or with steel wire amour when it is electrified with alternating current and shall not be laid in magnetic ducts.
Electric specifications
Rated voltage of cable
0.6/1kV
D.C. resistance of core
According to GB/T3856-1997 or IEC228A-82
Power frequency withstand voltage test for 5 minutes
No breakdown at 3.5kV
Hot set test for insulation, 200℃ 15min with pressure 20N/cm2
 
Maximum elongation values at load
175%
Maximum permanent elongation values after being cooled
15%
Power frequency withstand voltage test for 4 hours, not break down
2.4