Specifications:
- Accuracy class : 0.05
- Easy to calibrate closed I-P link meters with isolated current transformer(ICT)
Technical spec. |
YC1893D-ICT-6 |
YC1893D-ICT-12 |
YC1893D-ICT-24 |
YC1893D-ICT-48 |
ICT |
6 |
12 |
24 |
48 |
Accuracy class of ICT |
0.05 / 0.01 |
|||
Accuracy |
0.05 |
|||
Power Source |
YCS-103-250 |
YCS-103-600 |
YCS-103-1200 |
YCS-103-2500 |
Standard Meter |
SZ03A-K6 / SZ03A-K8 (customized) |
|||
Scanning Head |
YCG-S Series |
|||
Voltage |
||||
Test voltage output(Phase-Neutral) |
3x(24V~288V)(or customized) |
|||
Power of the voltage output |
Max. 3x100VA |
Max. 3x250VA |
Max. 3x500VA |
Max. 3x1000VA |
Resolution |
Better than 0.01% of full scale value of range |
|||
Setting accuracy |
Better than 0.05% at the final range value |
|||
Stability |
Better than 0.005% /h (integration time 150s) |
|||
Load regulation from 0~max. load |
Better than 0.01% |
|||
Distortion factor |
Better than 0.3% for linear resistance load |
|||
Harmonic |
2nd~21st free programmable |
|||
Current |
||||
Test current output |
3x(1mA~100A) |
|||
Power of the current output |
Max. 3x150VA |
Max. 3x350VA |
Max. 3x750VA |
Max. 3x1500VA |
Resolution |
Better than 0.01% of full scale value of range |
|||
Setting accuracy |
Better than 0.05% at the final range value |
|||
Stability |
Better than 0.005% /h (integration time 150s) |
|||
Load regulation from 0~max. load |
Better than 0.01% |
|||
Distortion factor |
Better than 0.3% for linear resistance load |
|||
Harmonic |
2nd~21st free programmable |
|||
Phase angle |
||||
Range |
0~360 |
|||
Resolution |
0.01 |
|||
Setting accuracy |
0.1 |
|||
Frequency |
||||
Range |
45Hz~65Hz |
|||
Resolution |
0.01Hz |
|||
Error display |
||||
Type of error display |
Red LED |
|||
Resolution of error displays |
8 digitals |
|||
Other |
||||
Voltage supply |
3x220/380V±10%(or customized) 50/60Hz ±2Hz |
|||
Ambient temperature |
-10°C~+40°C |
|||
Relative humidity |
35%~85% |
Description:
- Installing the ICT in each meter position to test three-phase meters with closed links between the current and voltage measuring circuits(I-P links)
- The meter test system can measure mechanical meter, electronic mechanical meters and electronic meter by ways of automatic, semi-automatic or manual operation.
- Meters under testing: 3P4W, 3P3W, 1P2W
- Testing mode: active power, reactive power, cross connected reactive power
- Simultaneously measure meters with same specifications but different meter constants
- Automatic positioning rotor mark of disc of mechanical meter, with more efficiency.
- Starting test and creeping test
- With the protection function of overload, short voltage circuit and open current circuit.
- The swing together of the scanning heads simplifies the control.
- Aluminum alloy material, light and strong and corrosion resistant
- The testing software with friendly Windows 2000 /XP /7 /8 /10 operation system, includes functional module of all kinds of modern energy meter needed, to reality error test, harmonic test, demand test, influence test etc,.
Applications:
- Nation-level utility companies
- Governmental bureaus of metrology
- Big energy meter manufacturers
Company Development History
- 1987, the company was formally established.
- 1989, single phase EEM calibrator launched.
- 1990, three phase EEM calibrator launched.
- 1995, the first company manufacturing EEM calibrator of 0.01 grade.
- 1999, exporting the EEM calibrator to Schlumberger Co (France), started the international business.
- 2000, multi-function standard meter of sampling technology was sold overseas.
- 2002, 0.02 grade standard meter was developed and put into market. The first company in China authorized to manufacture high class metering products
- 2003, ranked in the Guangzhou 120 most grown enterprise.
- 2004, ranked in the Guangzhou 100 strongest private enterprises.
- 2006, the products successfully export to 30 countries and areas.
- 2007, got Innovative Award of China Private Science & Technology Company