Item Name: ZN28A-12 series Indood Vacuum Circuit Breaker
As indoor AC hignvoltage switchgear of rated voltage of 12KV and three -phase 50Hz, the ZN28A-12 Series indoor AC high voltage vacuum circuit breaker mainly serves in the fixed type switchgear or removable switchgear for replacing the oil-minimum circuit-breaker inside backward switchgear. The circuit-breaker can function ad protection and control device for electic equipment in mineral& industrial enterprise, power plant and substation and the occasions featuring frequent operation.
Standard: GB1984, jb3885, DL/T403.
As indoor AC hignvoltage switchgear of rated voltage of 12KV and three -phase 50Hz, the ZN28A-12 Series indoor AC high voltage vacuum circuit breaker mainly serves in the fixed type switchgear or removable switchgear for replacing the oil-minimum circuit-breaker inside backward switchgear. The circuit-breaker can function ad protection and control device for electic equipment in mineral& industrial enterprise, power plant and substation and the occasions featuring frequent operation.
Standard: GB1984, jb3885, DL/T403.
Item | Unit | Data | ||||
20kA | 25kA | 31.5kA | 40kA | |||
Rated Voltage | kV | 12 | ||||
Rated Current | A | 630, 1250 | 630, 1250, 1600 | 1250, 1600, 2000 | 2000, 2500, 3150 | |
Rated short-circuit breaking current | kA | 20 | 25 | 31.5 | 40 | |
Rated short-circuit making current(peak) | kA | 50 | 63 | 80 | 100 | |
Rated peak withstand current | kA | 50 | 63 | 80 | 100 | |
4S Rated short-time withstand current | kV | 20 | 25 | 31.5 | 40 | |
Rated insulating level | power frequency withstand voltage(rated open circuit before and later) | kV | 42 | |||
Impulse withstand voltage(rated open circuit before and later) | kV | 75 | ||||
Rated operating order | O-0.3S-CO-180S-CO | O-180S-CO-180S-CO | ||||
Mechanical life | time | 10000 | ||||
Breaking times of rated short-circuit breaking current | time | 30 | 20 | |||
Contact opening size | mm | 11±1 | ||||
Overtravel | mm | 4±1 | ||||
Different period of three-phase switch on and off | ms | ≤2 | ||||
Spring jumping time of contact switch on | ms | ≤2 | ||||
Average switch-off speed | m/s | 1.2±0.3 | ||||
Average switch-on speed | m/s | 0.6±0.2 | ||||
Switch-off time | Max operating voltage | s | ≤0.06 | |||
Min operating voltage | s | ≤0.08 | ||||
Switch-on time | s | ≤0.2 | ||||
Resistance of each phase main loop | μΩ | ≤50 |