Product name:
UV sensitive conventional flame detector
Model No: FNC-302-F2UV sensitive conventional flame detector
Base details:
The flame detector is particularly suited in applications where flames can be expected to develop initially rather than smoke.
The flame detector has a single UV sensor with a narrow spectral response in order to discriminate between flames and most spurious sources of radiation and is designed for internal fully enclosed areas. Caution: The detector will also detect electrical discharges from lightning or arc welding.
Features:
1) 2-Wire operation
2) Low standby current and wide operating voltage
3) Fast-respond to all flames
4) Artistic housing design and 360 degree visible angle.
5) Comply with EN 54-10
Specification:
MODEL | FNC-302-F2 |
DETECTOR CLASS | Flame (185 to 260) |
SUPPLY WIRING | 2 – WIRE Polarity Insensitive |
DESIGN STANDARD | EN 54-10 |
SUPPLY VOLTAGE | 9 to 26V DC |
QUIESCENT CURRENT | 30μA @24V |
ALARM CURRENT | 50mA@24V |
TEMPERATURE RANGE | -10℃ to +55℃ |
HUMIDITY | 0% to 95% RH No Condensation |
UV SENSITIVITY | 185 To 260 nm |
RESPONSE TIME | 5Sec for 30mm flame @ 5 meters |
START-UP TIME | 10 Seconds |
DIMENSIONS (dia. x height) | 102 x 45mm (with Base) |
WEIGHTS | 150g (with Base) |
Schematic wiring diagram: