Application for URD Cable:
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% insulation level. Suitable for either direct burial or installation in ducts.
Construction for URD cable:
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, TRXLPE (tree-retardant cross-linked polyethylene) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.
Standard:
- AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV
- ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000V
- ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
- ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Options for URD cable. - EPR insulation
- Filled strand
- Cable core water blocking
Code name | Size AWG | Stranding | Neutral No. of Wire | Neutral Size AWG | Conductor diameter | Diameter over insulation shield | |||
Titan | 2 | 7 | 16 | 14 | 0.283 Inches | 0.775 Inches | 0.902 Inches | 1.003 Inches | 642 Lbs |
Monet | 1 | 19 | 13 | 12 | 0.322 Inches | 0.810 Inches | 0.972 Inches | 1.072 Inches | 504 Lbs |
Raphael | 1/0 | 19 | 16 | 12 | 0.362 Inches | 0.850 Inches | 1.012 Inches | 1.112 Inches | 923 Lbs |
Rubens | 2/0 | 19 | 20 | 12 | 0.405 Inches | 0.895 Inches | 1.057 Inches | 1.157 Inches | 1107 Lbs |
Bruegel | 3/0 | 19 | 25 | 12 | 0.456 Inches | 0.945 Inches | 1.107 Inches | 1.207 Inches | 1334 Lbs |
N/A | 4/0 | 19 | 32 | 12 | 0.512 Inches | 1.000 Inches | 1.162 Inches | 1.262 Inches | 1642 Lbs |