Basic Info.
  • Brand Name: sinopower 
  • 20MVA 35KV: SCZ10-20000-35 three phase big capacity cast resin transformer 
  • air-immersed transformer: mine dry-type transformer 
  • SC9: Dry type Transformer 
  • Model No.: SCZ10-20000-35 
  • Place of Origin: Zhejiang  
  • Min.Order: 1 Piece/Pieces
  • Means of Transport: Ocean
Supply Capacity
  • Production Capacity: 6000PCS
  • Packing:Naked Packing
  • Delivery Date: 6 months

Details

Type SC(B)10-50~3150KVA  35kV Class Distribution Transformer


Type

PO

PK25℃

I0

UK

LPA

w

w

%

%

dB(A)

SC10-50/35

440

1280

2.0











6




48

SC10-80/35

520

1610

2.0

48

SC10-100/35

620

1820

1.6

48

SC10-125/35

720

2250

1.6

48

SC10-160/35

780

2600

1.2

48

SC10-200/35

900

2920

1.2

48

SC10-250/35

980

3300

1.2

48

SC10-315/35

1160

3920

1.0

48

SC10-400/35

1360

4700

1.0

48

SC10-500/35

1600

5770

1.0

50

SC10-630/35

1840

6680

0.8

50

SCB10-800/30

2160

7920

0.8

50

SCB10-1000/35

2400

9070

0.6

50

SCB10-1250/35

2800

11060

0.6

50

SCB10-1600/35

3200

13440

0.5

52

SCB10-2000/35

3780

15830

0.5

52

SCB10-2500/35

4400

18970

0.4

52

resin cast dry-type transformer

Item

Meter type

Serial No.

Measurement

Scope

Accuracy

Meter

State

Calibration

Organization

Equipment

Validity

1

Insulation   resistance testing meter(MIT520)

ER-04-34

1MQ-5TQ

5

OK

Changzhou   Measurement Co.

Mar. 9 ,2013

2

Insulation   resistance testing meter(MIT520/2)

ER-04-09

1MQ-5TQ

v

OK

Changzhou   Measurement Co.

Mar. 9 ,2013

3

Automatic   anti-interference medium (AI-6000)

A91131A

3-6000PF tg5:   *1%+0.0004

1

OK

Shanghai Electric   Instrument Checking & Testing Station

Mar. 15 ,2013

4

Transformer turn   ratio testing meter (JYT)

04090552

1〜5000

0.2

OK

Changzhou   Measurement Co.

Mar. 9 ,2013

5

Infrared measure   temperature meter (FLUKE-62)

TT-10-119

-30oC〜500 oC

1

OK

Liyang   Measurement Co.

Apr 18,2012

6

DC resistance   testing meter (JYR-40D)

01091983

100uQ〜4Q

0.2

OK

Changzhou   Measurement Co.

Mar. 9 ,2013

7

DC resistance   testing meter (JYR-40D)

01091887

100uQ〜4Q

0.2

OK

Changzhou   Measurement Co.

Mar. 9 ,2013

8

Power-frequency   capacitance voltage divider (TRF-550)

090857

550 kV

1

OK

National HV   Measurement Station

Aug. 5 ,2013

9

Power-frequency   excitation transformer

090853

/

/

OK

/

/


(ZB-75/2*6.5)







10

Power-frequency   capacitance voltage divider (compound power-frequency support transformer)   YDTW-150

090862

150 kV

1class

OK

National HV   Measurement Station

Aug. 5 ,2013

11

Power-frequency   reactor (YDGK-2750/2*275)

090854

/

/

OK

/

/

12

Feebleness damp   capacitance voltage divider(compound lightning impulse withstand 4000KV)   FYI-1000/400

S0927-3

0〜3600kV

1

OK

National HV   Measurement Station

Aug. 5 ,2013

13

Feebleness damp   capacitance voltage divider(compound lightning impulse withstand 1200KV)   FYI-1000/500

S0937-5

0〜1200kV

1

OK

National HV   Measurement Station

Aug. 5 ,2013

14

Precision VT   (HJL-110)

0981

0982

0983

6KV〜110 kV/100V

0.01

OK

Northeast   National Measurement Co.

May. 27,2013

15

Precision VT   (HJL-110)

984      0986

0985

6KV〜110 kV/100V

0.01

OK

Northeast   National Measurement Co.

May. 27,20131

16

Precision CT   (HJL-110)

0986

0985

0984

5〜3000/5A

0.01

OK

Northeast   National Measurement Co.

May. 27,2013

17

Precision CT   (HJL-110)

0983

0982

0981

5〜3000/5A

0.01

OK

Northeast National   Measurement Co.

May. 27,2013

18

Power analyzing   meter (WT3000)

91HA17572

1000V, 20A

0.02

OK

Shanghai   Measurement Co.

Jan. 18,2013

19

Power analyzing   meter (WT3000)

91HA17573

1000V, 20A

0.02

OK

Shanghai   Measurement Co.

Mar. 15 ,2013

20

Multicenter   digital partial discharge meter (TWPD-2B)

0905XY223

0.1~106pC

3

OK

Shanghai Electric   Instrument Checking & Testing Station

Nov 10, 2012

21

Multicenter   digital partial discharge meter (TWPD-4)

0408XY38

0.1〜106pC

3

OK

Shanghai Electric   Instrument Checking &Testing Station

Mar. 15 ,2013

22

Standard pulse   generator (TWPD-02)

0908X04064

10〜500 pC

1

OK

Shanghai Electric   Instrument Checking & Testing Station

Nov 10, 2012

23

Sound measure   meter (AWA5661)

047090

24〜150dB

1

OK

Shanghai Measurement   Co.

Apr 18,2012

24

DOUBLE spectrum   analyzer(W5300)

BS-02-03

10Hz〜1M Hz

0.1

OK

Shanghai Electric   Instrument Checking & Testing Station

Nov 10, 2012

25

Temperature   Measuring Instrument

S5HB07150

-30°C 〜500°C

1

OK

Jiangsu Oriental   Aviation Calibration Testing CO.,LTD

Oct .14,2012



Send message to this supplier
Ms. Carro
Tel: 86-574-27906678
Mobile: +86-13566002198
Enter between 20 to 3,000 chatacters.
Contact Method
NINGBO SINOPOWER TECHNOLOGY CO.,LTD.
7-5 East Building, Technology & Trade Center, No.100 Xiangyun Road, National Hi-Tech Zone,, Ningbo, Zhejiang, China (Mainland) / 315040
Fax: 86-574-27906690
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!
Buyer Help Center