LCD Pure Sine Wave Uninterruptible Power Supply Online UPS 1Kva 2Kva 3Kva Networking

 

DSP Technology

Active input power factor correction (PFC)

Wide range of input voltage and frequency

Zero power switch delay

Active Load Management

Sufficient Expansion Slots

The load power factor is 0.8: it adapts the features of most current electric equipment and elevates the load-bearing capacity of the machines.

Support the Generators: The wide range of input voltage and frequency can effectively separate the harmful electric wave produces by the generators and provide safe and reliable power supply.

 

SAME SPECIFICATION AS CE1K CE1KS

 

Model# CA1K CA1KS Comments
Input voltage
Rated voltage  220VAC
Phase Single phase with ground
Turn on voltage range (90±5285±5)VAC
Bypass voltage range 80VAC~286VAC(default:80VAC~264VAC) Could be adjusted by software.
Bypass low loss  80VAC~220VAC(default:80VAC)
Bypass low comeback Low loss+10VAC
Bypass high loss 220VAC~286VAC(default:264VAC)
Bypass high comeback High loss -10VAC
Line low loss/comeback (90±5) VAC /(110±5) VAC load≤30 PF=0.7
(110±5)VAC/(125±5)VAC 30load≤60
(120±5) VAC /(135±5) VAC 60load≤70
(140±5) VAC /(155±5) VAC 70load≤80
(160±5) VAC /(170±5) VAC load80
(90±5) VAC /(110±5) VAC load≤30 PF=0.8
(110±5) VAC /(125±5) VAC 30load≤55
(130±5) VAC /(145±5) VAC 56load≤65
(150±5) VAC /(165±5) VAC 66load≤70
(160±5) VAC /(175±5) VAC load70
Line high loss/comeback (300±5)VAC/(285±5)VAC 0≤load100
Input frequency 
Rated frequency 50Hz
Frequency low loss (40~49)±0.2Hz(default:46Hz) Could be adjusted by software.
Frequency low comeback Frequency low loss + 0.5Hz
Frequency high loss (51~60)±0.2Hz(default:54Hz)
Frequency high comeback Frequency high loss - 0.5Hz
Input power factor
Input power factor 0.99 220VAC,full R load
Generator Support generator input Generator rating≥2*UPS rating
Input current
Rated current 5A 220VAC,full RCD load
Input THDI ≤10% 220VAC,full RCD load, The mains THDI≤4%
Output protection
Rating protection 10A  AC fuse
Output power
VA/watt 1000VA/700W~800W Could be adjusted by software.
Rated voltage 220VAC Pure Sine wave
Voltage range 200VAC/208VAC/220VAC/230VAC/240VAC Could be adjusted by software. 10% derating for 208VAC/200VAC.
Voltage regulation ±2
Voltage distortion ≤7 Full RCD load 220VAC;battery fully charged
≤4 Full R load
DC offset ≤±200mV
Transient response ≤9 R load 01000
≤6 R load 2010020
Transient recovery ≤60ms voltage recovery to 90% Full RCD load
Bypass output before turn-on Default:No Could be set by software.
Crest ration 3:01
Output frequency range
Normal mode 1,Same as input frequency(46Hz~54Hz)
2,50Hz(Input frequency>54Hz or  Input frequency<46Hz)
Battery mode
Send message to this supplier
Mr. Lisa Zhao
Tel: 86-755-83265608
Enter between 20 to 3,000 chatacters.
Contact Method
Shenzhen Zhongyuan Chuangda Technology Co., Ltd
Bldg. 3, Meiran Workshop, Haogong Building, Shenzhen, Guangdong, China (Mainland)
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!