Super-slim Compact Desgin Chilled Water Air Handling Units

 

Specifciations

 

 

Unit Model

EKSW

015D

EKSW

020D

EKSW

025D

EKSW

030D

EKSW

035D

EKSW

040D

EKSW

050D

Nominal air flow (m3/h) 1500 2000 2500 3000 3500 4000 5000
External static pressure (Pa) 70 100 100 120 120 150 150
Nominal cooling capacity (kW) Four rows of coils (in air return condition) 6 10 12 16 18 23 29
Four rows of coils (in fresh air condition)  19 27 31 40 47 57 70
Six rows of coils (in air return condition)  10 15 17 22 26 31 37
Six rows of coils (in fresh air condition) 25 34 39 49 61 70 84
Nominal heating capacity (kW) Four rows of coils (in air return condition) 11 16 19 24 28 34 42
Four rows of coils (in fresh air condition)  21 30 34 43 52 61 73
Six rows of coils (in air return condition)  15 21 23 29 36 42 50
Six rows of coils (in fresh air condition) 26 36 41 51 64 74 87
Nominal input power (W) Four rows of coils  373 614 787 797 905 1248 1533
Six rows of coils  397 653 823 845 1016 1362 1699
Nominal input current (A) Four rows of coils  1.72 2.96 3.61 3.62 4.22 5.68 6.98
Six rows of coils  1.81 3.01 3.78 3.96 5.1 6.29 7.86
Water flow (m3/h) Cooling
condition
Air return condition

1.01

(1.78)

1.77

(2.57)

2.40

(3.36)

3.13

(4.18)

3.09

(4.58)

3.91

(5.36)

5.32

(7.06)

Fresh air condition

3.26

(4.30)

4.69

(5.95)

6.07

(7.61)

7.65

(9.29)

8.21

(10.5)

9.78

(12.15)

12.89

(15.59)

Heating
condition
Air return condition

0.96

(1.27)

1.38

(1.78)

1.80

(2.28)

2.27

(2.79)

2.42

(3.14)

2.91

(3.64)

3.83

(4.69)

Fresh air condition

1.85

(2.30)

2.57

(3.14)

3.26

(3.98)

4.07

(4.84)

4.47

(5.52)

5.28

(6.36)

6.83

(8.10)

Water resistance (kPa) Cooling
condition
Air return condition 5(14) 14(27) 24(54) 14(21) 13(44) 25(45) 40(75)
Fresh air condition 39(77) 40(89) 46(96) 32(76) 36(79) 46(103) 74(113)
Heating
condition
Air return condition 4(12) 12(24) 10(24) 9(12) 11(32) 19(30) 24(32)
Fresh air condition 20(42) 26(49) 24(62)
Send message to this supplier
Mr. Rocky
Tel: 86-769-83660888
Enter between 20 to 3,000 chatacters.
Contact Method
EuroKlimat Air Conditioning Refrigeration Company
Euroklimat Industrial Park, Dongguan, Guangdong, China (Mainland)
Related Products
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!