Double skin Return air handling units with 4-8 rows cooling coil air flow 2,000-400,000 m3h

 

 

EKDM air flow range is from 1000m3/h to 400000m3/h. Available functional sections include fresh/return air mixing section, cooling section, heating section, primary/medium/high efficiency filter section, electric heating section, humidifying section, sound attenuation section, heat recovery section, secondary air-return section, fan section, air diffuser section etc. Different combinations can meet different air handling requirements.

 

•   The surface  of the unit is made of quality color steel, which can resist corrosion, scratch and ultraviolet radiation.


•    Internal panels are made of steel plates galvanized  with aluminum and zinc, with an assured  service life of more than 15 years. All panels  feature  end-to-end  joints and smooth surfaces, without any bur or corroded point.


•    The internal panels feature reinforced design, which is strong enough to support the largest  air handling unit.


•    The unit panel  has two thicknesses,  namely  30mm and 50mm.Inside  the panel, hermetically foamed polyurethane (no fluorine) with a density of 48kg/m3 is used as the heat- insulating material. The heat conductivity factor is less than 0.02W/m°C.


•    Each functional section of the unit is equipped  with a steel trough base, thus  ensuring  it is well supported,  easy to transport and assemble. The overall robustness of the unit meets the  standard of CEN2.

 

 

Specifciations 

 

Unit model EKDM Rated air flow m3/h 4 rows 6 rows 8 rows
Total cooling capacity kW Water flow l/s

Water resi-

stance kPa

Pipe diameter DN Total cooling capacity kW Water flow l/s

Water resi-

stance kPa

Pipe diameter DN Total cooling capacity kW Water flow l/s Water resi-stance kPa Pipe diameter DN
306 2000 12 0.5 6 40 16 0.7 15 40 18 0.8 26 40
406 3000 17 0.8 7 40 23 1.1 16 40 27 1.3 27 40
407 4000 23 1.1 13 40 31 1.5 32 40 36 1.7 51 40
408 5000 29 1.4 20 40 38 1.8 48 40 42 2.0 29 40
508 6000 36 1.7 20 40 48 2.3 48 40 52 2.5 23 50
607 7000 39 1.9 17 40 53 2.5 38 40 61 2.8 58 50
608 8000 47 2.2 24 40 62 3.0 58 40 68 3.2 26 50
511 9000 57 2.7 57 40 70 3.3 37 40 78 3.8 31 50
610 10000 64 3.1 51 40 76 3.6 29 50 89 4.3 51 50
611 12000 70 3.4 20 40 92 4.4 44 50 103 5.0 38 50
712 15000 90 4.3 23 50 119 5.8 55 65 131 6.3 44 65
812 18000 107 5.2 27 65 141 6.8 60 65 157 7.6 51 65
813 20000
Send message to this supplier
Mr. Rocky
Tel: 86-769-83660888
Enter between 20 to 3,000 chatacters.
Contact Method
EuroKlimat Air Conditioning Refrigeration Company
Euroklimat Industrial Park, Dongguan, Guangdong, China (Mainland)
Related Products
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!