CT and PT Analyzer

Price: 2.0 USD
Trade Term: FOB
Payment Terms: T/T,L/C,D/A,D/P,WU,Paypal,Money Gram
Trade on HiSupplier, Worry Free Guarantee
Trading safety, secure your money, lower the risk, protect both buyers and suppliers
HiSupplier is a Chinese multinational company in U.S, it helps to coordination and order landing.
More ›
  • Product Details
  • Company Profile
  • Product Reviews
Basic Info.
  • Tester: Transformer Tester 
  • PT Analyzer: CT Analyzer 
  • Current Transform Analyzer: Power Analyzer 
  • Model No.: GDVA-405 
  • Place of Origin: Chongqing  
  • Min.Order: 1 Set/Sets
  • Means of Transport: Ocean, Air, Land
Supply Capacity
  • Production Capacity: 500Sets/per Month
  • Packing:Wooden Case
  • Delivery Date: 10days

GDVA-405 CT PT Analyzer

Introduction:

Tests for Current Transformer:

l  Excitation curve and parameters test

l  Turns ratio test

l  Ratio and phase error test

l  Polarity mark check

l  Winding resistance measurement

l  Secondary loop burden measurement

l  Error line curve test for protection CT

l  Transient CT parameters test

l  CT nameplate guess

l  Saturation hysteresis loop curve measurement

l Tests for Potencial Transformer:

l  Turns ratio test

l  Ratio error and phase angle error test

l  Polarity test

l  Secondary burden test

l  Winding resistance test

Applications of CT/ PT Analyzer:

l  CT nameplate check

l  CT parameters check in work burden

l  CT transient parameters analysis

l  CT ratio and phase error calibration

l  PT routine test

Specifications:

Test standards

IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13

Power supply

 AC220V±10%, 50/60Hz±10%

Voltage output

 0.1~180V (AC)

Current output

 0.001~5A(RMS)

Power output

 500VA

Max.  knee voltage measurement

 45KV

Current measurement

 

 

  Range

0~10A (automatically change  range in 0.1/0.4/2/10A)

  Error

 <±0.1%+0.01%FS

 

Voltage measurement

 

 Range

0~200V (automatically change range in 1V/10V/70V/200V)

 Error

< ±0.1%+0.01%FS

Turns ratio measurement Range

  

1~35000

1~2000, error<0.05%

2000~5000,error<0.1%

5000~35000,error<0.2%

Phase measurement  

error

 ±2min

resolution

 0.01min

Winding resistance measurement

    

   

Range

0~8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm)

Error

 < 0.2%RDG+0.02%FS

Maximum resolution :  0.1mΩ

Temperature measurement

-50~100 Celsius degree; error<3 Celsius degree

CT Secondary burden

Range

0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

Error

 <0.2%RDG+0.02%FS

Maximum resolution : 0.001ohm

   

  

PT Secondary burden

 

Error

0~80kohm (automatically change range in 800ohm/8kohm/80kohm)

Maximum

<0.2%RDG+0.02%FS

resolution

 0.1ohm

   

PT ratio measurement

 

Range

1~35000

1~10000 error<0.1%

10000~35000 error<0.2%

PT ratio error measurement :Typical error <0.05%,

Maximum Error<0.1%

PT phase angle measurement maximum error < 3min

Make evaluation for test results according to selected standards

Make word report for test result

Make word reports one time for multi-group test records on the PC

Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test

Compare excitation curves with saved excitation curves in the same window

Memory capacity

 >1000 groups test results

Working condition temperature

 -10℃~50℃; moist ≤90%



Send message to this supplier
Ms. cathy Jiang
Tel: 86-023-62984891
Enter between 20 to 3,000 chatacters.
Contact Method
Gold Co.,Ltd
9F/10,Jintai Building,Nanping, Chongqing, China (Mainland)
Didn't find what you're looking for? Post Buying Lead or contact our customer service specialist for help!
Buyer Help Center