Medium Voltage 26/35kV AL/XLPE/CTS/PVC with Stranded Conductor Rigid

 

Applications: XLPE Insulated Cable is used as power distribution and transmission line at rated voltage 26/35kV.

 

Construction:

Conductor  Aluminum Conductor as per IEC 60228,Class 2
Circular or Shaped conductor
Flexible conductor(class 5) optional.
Insulation XLPE (Cross-Linked Polyethylene) rated at 90,many color optional
Metallic Screen optional Copper tape or copper wires braiding optional
Sheath PVC or FR-PVC type ST2 to IEC 60502, black or red or customization

 

Ordering Advice

 

Rated Voltage

Application Standard: IEC/BS/UL/GB

Number of Cores

Conductor Size & Construction

Type of Insulation

Armored or unarmored. If armor, the armor type & material

The Requirement of Sheath

Length of Cable & Packing Requirement

Other Requirement

 

 

Technical data: Rated voltage:26/35kV Medium Voltage

Maximum Conductor Temperature: under normal (90), emergency (130) or short circuit no more than 5 s (250) conditions.

Min. Ambient Temp. 0 OC, after installation and only when cable is in a fixed position

Min. Bending Radius: 20 x cable O.D for single core without armor

15 x cable O.D for multi core without armor

15 x cable O.D for single core with armor

12 x cable O.D for multi core with armor

 

Standards: International: IEC 60502-2, IEC 60228, (IEC 60332-3 for FR-type only)

China: GB/T 12706, (GB/T 18380-3 for FR-type only)

Other standards such as BS, DIN, VDE and ICEA upon request

 

Technical parameter:

 

Nom. Cross-section of conductor Strands No./Dia. Of Conductor Insulation Thickness Sheath Thickness Approx. O.D.

Approx.

Weight

Max. D.C Resistance of Conductor (20 ) Testing Voltage A.C Current Rating
mm2 pc/mm mm mm mm kg/km Ω /km kV/5min In air (A) In soil(A)
1 × 50 7/3.07 10.5 2.2 39.0 1449 0.641 91 170 165
1 × 70 19/2.20 10.5 2.4 41.0 1604 0.443 91 210 200
1 × 95 19/2.56 10.5 2.4 42.0 1767 0.320 91 255 240
1 × 120 19/2.86 10.5 2.4 44.0 1923 0.253 91 290 270
1 × 150 19/3.20 10.5 2.5 45.0 2103 0.206 91 330 305
1 × 185 37/2.52 10.5 2.5 47.0 2282 0.164 91 380 345
1 × 240 372.56 10.5 2.6 49.0 2584 0.125 91 435 400
1 × 300