Features
External (key-switch operated):
Reset/resound/test zone lamps evacuate
Silence alarm sounders
Silence fault sounders
One man detector test
Zone isolate
Revert to short-circuit: fire (no resistors in call points)
Sounder fault
Battery/power supply fault
Mains on
Zone fire
Zone fault
Open circuit zone fault
Short circuit zone fault
Zone isolated
Engineer test selected
Two sounder circuits (alarm relay contacts can be obtained by connecting a relay to a sounder circuit)
Repeater panels
Multiple sounder outputs
Connection to landlord panel
Internal:
External indicators:
Internal indicators:
Outputs:
Ancillary connections for expansion modules will allow the following:
Specifications
2 (0.8A SUPPLY) | 4 / 6 (1.5A SUPPLY) | 8/10/12/14/16/18 (4.0A SUPPLY) | |
POWER SPECIFICATION | |||
MAINS SUPPLY VOLTAGE | 230V±10%Va.c.50/60Hz | 230V±10%Va.c.50/60Hz | 230V±10%Va.c.50/60Hz |
INTERNAL POWER SUPPLY | 27 Vd.c. | 27 Vd.c. | 27 Vd.c. |
TOTAL OUTPUT CURRENT LIMITED TO | 800mA@240VAC | 1500mA@240VAC | 4000mA@240VAC |
AUXILIARY POWER OUTPUT | 27 Vd.c. | 27 Vd.c. | 27 Vd.c. |
MAINS SUPPLY MONITORED FOR FAILURE | YES | YES | YES |
BATTERY CHARGER MONITORED FOR FAILURE | YES | YES | YES |
BATTERIES MONITORED FOR DISCONNECTION AND FAILURE | YES | YES | YES |
DETECTOR CIRCUIT SPECIFICATION | |||
NUMBER OF CIRCUITS | 2 | 4 or 6 | 8, 10, 12, 14,16,or 18 |
LINE FAULT MONITORED FOR OPEN CIRCUIT | YES | YES | YES |
LINE FAULT MONITORED FOR SHORT CIRCUIT | YES (Can be disabled) | YES (Can be disabled) | YES (Can be disabled) |
LINE FAULT MONITORED FOR DETECTOR REMOVAL | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | ||
END OF LINE RESISTOR (SUPPLIED) VALUE | 6800Ω,5% tolerance,0.25W | 6800Ω,5% tolerance,0.25W | 6800Ω,5% tolerance,0.25W |
DETECTOR CONTINUITY DIODES | Silicon 1N4001 or Schottky type(required if End of Line Monitor Unit fitted to give Detector Removal Fault) | ||
CALL POINT RESISTOR VALUE (NOT SUPPLIED) | 470 to 680Ω, 0.5W | 470 to 680Ω, 0.5W | 470 to 680Ω, 0.5W |
MAXIMUM NUMBER OF SMOKE DETECTORS PER ZONE | 20(maximum detector current = 2mA) | 20(maximum detector current = 2mA) | 20(maximum detector current = 2mA) |
MAXIMUM NUMBER OF MANUAL CALL POINTS PER ZONE | No limit | No limit | No limit |
SOUNDER CIRCUIT SPECIFICATION | |||
NUMBER OF CIRCUITS | 2 | 2 | 2 |
END OF LINE RESISTOR VALUE | 6800Ω, 5%tolerance,0.25W | 6800Ω, 5%tolerance,0.25W | 6800Ω, 5%tolerance,0.25W |
LINE FAULT MONITORED FOR OPEN CIRCUIT | YES | YES | YES |
LINE FAULT MONITORED FOR SHORT CIRCUIT | YES | YES | YES |
OUTPUTS FUSED AT | 1 Amp | 1 Amp | 1.6 Amp |
MAXIMUM TOTAL OUTPUT CURRENT ALL OUTPUTS | 800mA | 1500mA | 4000mA |
MAXIMUM NO OF BELLS @ 25 mA EACH BELL | 32 | 56 | 120 |
MAXIMUM NO OF ELECTRONIC SOUNDERS @ 20 mA | 40 | 70 | 150 |
AUXILIARY RELAY CONTACTS (DO NOT CONNECT MAINS VOLTAGES) | 1A 30 Vd.c. max Voltage Free | 1A 31 Vd.c. max Voltage Free | 1A 32 Vd.c. max Voltage Free |
FUSES-ALL FUSES COMPLIANT TO IEC (EN60127 PT2) | |||
MAINS TERMINAL BLOCK | 200mA T 20 mm | 400mA T 20mm | 630mA T 20mm |
SOUNDER OUTPUTS | 1A F 20mm | 1A F 20mm | 1.6A F 20mm |
AUXILIARY OUTPUT | 1A F 20mm | 1A F 20mm | 1A F 20mm |
BATTERY FUSE | 1.6A F 20mm | 1.6A F 20mm | 3A F 20mm |
DOOR RETAINING MAGNETS | DO NOT USE PANEL POWER SUPPLY AS YOU WILL DRASTICALLY REDUCE BATTERY STAND-BY TIME | ||
CONNECTION BLOCK | |||
LARGEST ACCEPTABLE CONDUCTOR SIZE | 2.5mm2 | 2.5mm2 | 2.5mm2 |
SMALLEST ACCEPTABLE CONDUCTOR SIZE | 0.75mm2 | 0.75mm2 | 0.75mm2 |
DIMENSIONS | |||
ENCLOSURE(WIDTH x HEIGHT x DEPTH) | 415 x 265 x 100mm | 415 x 265 x 100mm | 415 x 265 x 100mm |
WEIGHT(WITHOUT BATTERIES) | 5100g | 5200g | 5500g |