High Frequency online ups (1KVAL-3KVAL)
Model | C1KL | C2KL | C3KL | ||
Rated Power | VA/W | 1KVAL/700W | 2KVAL/1400W | 3KVAL/2100W | |
INPUT | Nominal Voltage | 220VAC | |||
Range | |||||
Voltage Range | 115 ~ 300VAC | ||||
Frequency Range | 46~54Hz(default), user adjustable within 40~60Hz | ||||
Power Factor | 0.97 | ||||
OUTPUT | Voltage | 220VAC ±2% | |||
Frequency | 50Hz±1 Hz | ||||
Waveform | Sine Wave | ||||
Distortion | 3% | 4% | |||
Overload capability | 108%~150% for 30 sec., 150% for 300 ms | ||||
Current Crest Ratio | 3:1 max. | ||||
Battery | Type | Sealed, Maintenance free, Lead-Acid | |||
Nominal DC Voltage | 36V | 96V | |||
Back-up time | Depends on the capacity of the external battery bank | ||||
Connection | External Battery | ||||
Transfer time | 0 ms; less than 4 ms from inverter to bypass and vice versa | ||||
LED indicators | Status | Load level/Battery level, Battery , Utility power, Inverter, Bypass, Overload, Fault | |||
Audible alarm | Bypass | Alarm beeps every two minutes | |||
Battery discharge | Alarm beeps every four seconds, every second if battery low | ||||
Overload | Alarm beeps two for every second | ||||
Fault | Alarm beeps continuously | ||||
Acoustic noise | At 1 meter distance | £ 45 dBA | £ 50 dBA | ||
Communications | DB-9 Port | RS232 serial interface | |||
Environmental | Operating temperature | 0 ~ 40°C | |||
Operating humidity | 20% ~ 90% non-condensing |