AQ Series
- Low cost solution to powerline noise at high frequencies
- High common and differentialmode performance from 10KHz to 1GHz
- Available with an IEC inlet,fuseholder and switch
- Ideal for applications wherecomputers are used to process secret or confidential information
Ordering Information
Available Part Numbers
3VAQ3 | 6VAQ3 |
3VAQ8F | 6VAQ8F |
3VAQ8FS | 6VAQ8FS |
Specifications
Maximum leakagecurrent, each Line to Ground: | |||
3A Models | 6A Models | ||
@ 120 VAC 60 Hz | 1.2mA | .7mA | |
@ 250 VAC 50 Hz | 2.3mA | 1.2mA | |
Hipot rating (oneminute): | |||
Line to Ground | 2250 VDC | ||
Line to Line | 1450 VDC | ||
Operating Frequency: | 50 / 60 Hz | ||
Rated voltage(max.): | 250 VAC | ||
Rated Current: | 3 or 6 Amps | ||
Operating Ambient Temperature Range(at rated current Ir): | |||
-10°C to +40°C | |||
In an ambienttemperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir √(85-Ta)/45 |
Electrical Schematic
3A Models
6A Models
Accessories
GA400: NEMA 5-15P to IEC 60320-1 C13 line cord
Case Styles
Case Styles
3VAQ3
3VAQ8F
3VAQ8FS
6VAQ3
6VAQ8F
6VAQ8FS
Recommended Panel Cutouts
Performance Data
Typical Insertion Loss
Measured in closed 50 ohm system
Typical Insertion Loss
Measured in closed 50 ohm system
3VAQ
6VAQ
Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
Common Mode / Asymmetrical (Line to Ground)
Differential Mode / Symmetrical (Line to Line)
Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
Common Mode / Asymmetrical (Line to Ground)
Current Rating | Frequency - MHz | ||||||||
.01 | .1 | .5 | 1 | 10 | 50 | 100 | 300 | 1000 | |
3A | 10 | 80 | 88 | 88 | 100 | 100 | 100 | 93 | 85 |
6A | 26 | 59 | 80 | 80 | 100 | 100 | 100 | 93 | 85 |
Differential Mode / Symmetrical (Line to Line)
Current Rating | Frequency - MHz | ||||||||
..01 | .1 | 1 | 10 | 30 | 100 | 300 | 300 | 1000 | |
3A | 6 | 51 | 78 | 88 | 100 | 100 | 100 | 93 | 85 |
6A | 10 | 65 | 86 | 95 | 100 | 100 | 100 | 93 | 85 |