Specifications
Gas detected |
Ozone |
Sensing element |
Semiconductor ozone gas sensor |
Power Supply |
24VAC/VDC±10% |
Consumption |
2.2 W |
Temperature sensor |
NTC |
Warm up time |
96 hours (first time) 1 hour(operation) |
Signal Update |
2s |
O3 Measuring Range |
10~500ppb |
O3 measuring precision |
±15ppb + 20% reading (15~35/30~60%RH) |
Six indicator lights |
The first green indicator light:O3≤49ppb The first and the second green indicator lights:50ppb~99ppb The first yellow indicator light:100ppb~199ppb The first and the second yellow indicator lights:200ppb~299ppb The first red indicator light:300ppb~399ppb The first and the second indicator lights:O3 ≥400ppb |
Modbus interface |
Modbus RS485 protocol with19200bps(default), 15KV antistatic protection, independent base address, 31 max network nodes |
Relay output(optional) |
One dry contact output, rated switching current 2A(resistance load). Provide four ozone ranges to be selected to control the relay turn-on/turn-off (50ppb /100ppb-default / 200ppb/ 300ppb) |
Analog output(optional) |
1X0~10VDC or 4~20mA for ozone measurements |
Operation temperature |
550 (41122) |
Operation humidity |
080%RH,non condensing |
Weight |
190g |
Dimensions |
100mm×80mm×28mm |
Installation standard |
65mm×65mm or 2”×4” wire box |
Housing/ IP rate |
PC/ABS plastic fireproof material, IP30 |
Standard |
CE-Approval EN60730-1:2000 +A1:2004 + A16:2007 + A2:2008 Directive: 2004/108/EC |
Features
-
Real time detect and indicate indoor ozone level
-
Design temperature compensation for ozone measurements
-
Featured 6 LED lights indicates different ozone levels
-
Five years lifetime
-
Optional 1x dry contact output to control an O3 generator or 1xanalog output for ozone measurements
-
Modbus RS485 interface
-
Easy zero calibration
-
Higher performance with lower price
- CE-Approval
Applications
1. Specially used for detecting indoor ambiance quality
2. Real time measuring ozone level and analyzing: alarm when ozone level is over proof, control ozone concentrations by controlling related devices in order to reach a certain level in some special places
3. Anti-epidemic and disease prevention, sanitary inspection, environment protection, health protection, etc.
Dimensions and Mounting
Models Guide
ITEM |
MODEL |
DESCRIPTION |
Ozone Detector/Controller |
F2000TSM-O3-L100C |
Ozone indicator with 6 LED indicator lights Modbus RS485 interface |
F2000TSM-O3-L101C |
Ozone indicator with 6 LED indicator lights One dry contact output, Modbus RS485 interface |
|
F2000TSM-O3-L110C |
Ozone indicator with 6 LED indicator lights One analog output, Modbus RS485 interface |
Wiring Diagram