Specification
CO2 Sensor |
Non-Dispersive Infrared Detector (NDIR) |
Measurement Range |
02,000ppm/ 0~5,000ppm /0~50,000ppm (selectable in the order) |
Accuracy |
±40ppm + 3% of reading @22(72) |
Stability |
<2% of full scale over the life of the sensor |
Calibration |
Self-calibration system |
Response Time |
<5 minutes for 90% step change at low duct speed |
Non-linearity |
<1% of full scale @22(72) |
Duct Air Velocity |
0~450m/min |
Pressure Dependence |
0.135% of reading per mm Hg |
Temperature Dependence |
0.2% of full scale per ºC |
Warm up time |
24 hours (first time) 10 minutes (operation) |
Temperature & Humidity Sensor |
Temperature |
Relative Humidity |
Sensing element: |
Band-gap-senor |
Capacitive humidity sensor |
Measuring range |
0~50 |
0 -100%RH |
Accuracy |
±0.4 (0~50) |
±3%RH (20%-80%RH) |
Display resolution |
0.1 |
0.1%RH |
Stability |
±0.1per year |
±1%RH per year |
General Data |
|
Power supply |
24VAC/24VDC |
Consumption |
1.8 W max. ; 1.0 W avg. |
LCD display |
White backlit LCD display CO2 measurement or CO2 + temperature& humidity measurements |
Analog output |
1x0~10VDC or 4~20mA output for CO2 3x 0~10VDC or 4~20mA outputs for CO2+ Temperature +RH The voltage output or current output can be selectable by jumpers |
Modbus RS485 Interface |
19200bps, 15KV antistatic protection. |
Operation conditions |
0~50(32~122); 0~100%RH |
Storage conditions |
0~50(32~122)/ 5~95%RH |
Net weight |
320g |
IP class |
IP50 for models without LCD; IP40 for models with LCD |
Standard Approval |
CE-Approval |
Features
-
Special used to real-time detect CO2 concentration in air ducts.
-
NDIR infrared CO2 sensor inside with Self-Calibration and up to 15 years lifetime
-
Humidity and temperature detection optional
-
Digital combined temperature and humidity sensor provide the highest accuracy in full range
-
White backlit LCD display option can display CO2 measurement as well as temperature and RH measurements
-
Providing one or three 0~10VDC or 4~20mA analog outputs
-
Modbus RS485 communication interface optional
-
Smart structure and attractive housing provides you a unique operation feeling
-
Simple and skillful design and installation with a demountable and replaceable filter to provides dust-proof protection
-
Special a 180° rotatable fastness position for the probe can change the direction of air detection.
-
Provides a split type with an external sensor probe for some special applications
-
All housing and probe are IP54 class
- CE approval
-
HVAC systems of all commercial buildings and residential houses
-
Ventilation control system
-
Plant factories, greenhouses
-
Food stores, incubators
-
Other places where needs real time detection and control CO2 concentration
Dimensions & Mounting
Models Guide
Model Name |
Description |
|
CO2 Duct Probe Transmitter without LCD |
TG9106-02/05/20 |
1Xanalog output for CO2 measurement. -02: CO2 range 0~2000ppm -05: CO2 range 0~5000ppm -20: CO2 range 0~20,000ppm |
TG9116-02/05/20 |
1Xanalog output for CO2 measurement. Modbus RS485 interface |
|
TG9316-02/05/20 |
3Xanalog outputs for CO2 measurement, and temperature & humidity Modbus RS485 interface |
|
Didn't find what you're looking for?
Post Buying Lead or
contact our customer service specialist for help!
|