- For 3-phase, four wire, WYE Applications
- Filters each of the three lines plus the neutral and ground line
- Both common mode and differential mode suppression from 50kHz to 30MHz
- Effective for both balanced and unbalanced loads
- Ground choke included
- Optional end bell kits available to shield input and output terminals
- AYP single stage for lower noise environments
- AYT dual stage provides highest performance
Available Part Numbers
Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.
20AYP6C | 20AYT6C |
30AYP6C | 30AYT6C |
45AYP6C | 45AYT6C |
60AYP6C | 60AYT6C |
Specifications
Maximum leakage current, each Line to Ground: | ||
@ 120 VAC 60 Hz | 1.4 mA | |
@ 250 VAC 50 Hz | 3.4 mA | |
Hipot rating (one minute): | ||
Line to Ground | 1500 VAC | |
Neutral to Ground | 1500 VAC | |
Line to Neutral | 1450 VDC | |
Operating Frequency: | 50 / 60 Hz | |
Rated voltage (max.): | ||
Phase to Phase | 440 VAC | |
Phase to Neutral / Ground | 250 VAC | |
Rated Current: | 20A to 60A | |
Operating Ambient Temperature Range (at rated current Ir): | ||
-10°C to +40°C | ||
In an ambient temperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io = Ir √(85-Ta)/45 |